To set up the master and slave potentiometer settings on a SigmaGate, locate the below potentiometer dials.
DELAY: This sets the amount of time the gates will stay open after a customer has left through the gates and broke the PEC sensor beam. Range 0-8 seconds. Note: This timer will over ride the secure timer.
WRONG WAY: This timer is used to detect movement through the gates in the wrong direction. Please set to full right to avoid picking up a customers swinging arm. Range 0.1-2 seconds
SECURE: This timer will keep the gates open until the customer has passed through in the gates. Once the customers pass through the gates this timer is gets override by the DELAY timer. Range 0-32 seconds
PANIC FORCE: This dial sets the force required to slide the glass arm back into the body of the SigmaGate
On each gate, make the following adjustments:
- LEFT GATE
- Set DELAY, WRONG WAY, SECURE on the left hand gate to maximum/clockwise. (100%)
- Set PANIC FORCE to minimum/anticlockwise (0%)
- RIGHT GATE
- Set DELAY to half way. (50%) (4 seconds)
- Set WRONG WAY to maximum/ fully clockwise. (100%) (2 Seconds)
- Set SECURE to half way. (50%) (16 Seconds)
- Set PANIC FORCE to minimum/ fully anticlockwise. (0%)
NOTE: Turn all the way left (0%) then all the way right (100%) to determine where 50% is.
NOTE: In order for the Master and Slave function to be operational the gate configuration must be connected with GateCOM crossover cable (Saloon) to the opposing gate. Refer to SigmaGate Manual (attached).
Additional video
Recommended spare part
- If the Main PCB itself is faulty, below spare part can be ordered.